OUR WORK
FUEL TERMINAL OBSOLETE FIRE PUMP REPLACEMENT
CUSTOMER:
Fuel Terminal
JOB OVERVIEW:
A Fire Pump at a fuel terminal was performing badly during statutory testing.
The pump was removed from service and was found to be corroded badly.
The diesel driver was due for a major service and the decision was made to replace the pump and driver.
CHALLENGES
-
The model of pump was obsolete so like for like replacements not available.
-
Pipe modifications were required to meet the new pump flange positions.
-
The new diesel driver has a smaller footprint than the old one meaning base plate modifications were required for both driver
and pump.
SOLUTION:
-
Southern Cross ISO pump with a matching curve to the previous pump.
-
Internal epoxy ceramic coating applied to pump to prevent further corrosion issues.
-
New cummins diesel driver and flexible shaft coupling.
-
New suction and discharge manifold to connect new pump to existing pipework.
RESULT:
-
Pump and driver assembled on modified base plate and no plinth changes were required.
-
New pump was tested in the factory and exceeded original pumps’ performance and also complying with AS2941.